Hardwire translator zones are tampered or not learning in

  • Make sure resisters are installed 1-10k ohms for older translators, or 4.7k ohms required for the QS7133-840
  • Unplug transformer and battery (if applicable)
  • Press and hold memory reset button while simultaneously plugging power adapter in, hold for 5 seconds, left and right LEDs will blink
  • Press and hold EOL Learn button for 3 seconds. ALL Zone LEDs should flash ON then OFF. If they are off, the zones have been reset.
  • Trip each zone to calibrate
  • Press and hold EOL Learn button for 3 seconds to exit calibration mode
  • Open and close zones to test with the panel